AKKUTEC 24V 40A DC UPS 3 Phase input NBPAP33G1M01 : NBPAP33G1M01 AKKUTEC-2440-3P-DIN DC UPS 24V 40A Din Rail Mount 3 phase input lead acid battery based

AC/DC DC UPS Input: 400VAC 3 phase Output: 24V 40A Din rail Mount


Data Sheet (pdf)
Akkutec-2440 User Manual
Quick Installation Guide Akkutec 2440 (pdf)

Part #: AKKUTEC-2440-3P-DIN

Qty:

AKKUTEC 2440

  • Primary switched mode power supply with I/U-charging characteristics
  • Active power factor correction (PFC)
  • Microcontroller-supported battery management
  • Temperature tracking of the charging voltage by external sensor module (optional module)
  • Signal and control panel for control cabinet door mounting or surface mounting (option)
  • Art.-no. : NBPAP33G1M01

  • TECHNICAL DATA

    Input voltage : 3 x 400 V ... 500 V AC -15 % / + 10 %
    Frequency: 50/60 Hz
    Output voltage / Output current: 24 V DC / 40 A DC
    Dimensions (H x W x D): 233 x 292 x 138 mm
    Weight: 3,6 kg

    Technical Data

    Rated input voltage

    400 – 500 V AC

    Input voltage range

    360V - 550V « 400V-10% - 500V+10%

    Input frequency

    45 – 65 Hz

    Rated input current

    2,75 A ( 400V AC )

    2,2 A ( 500 V AC )

    Max. inrush current

    65A / 5ms, i²t = 14A²s

    System voltage

    24 V DC

    Output voltage

    (depending on state of charge of the battery)

    Voltage range

    - without temperature sensor

    - with temperature sensor

    a) 19,8 V DC...26,8 V DC

    b) 19,8 V DC …28,0 V DC

    Final charging voltage

    - without temperature sensor

    - with temperature sensor

    26,8 V DC ±0,4%

    27,1 V DC ±0,4% (at 25°C)

    Charging characteristics

    I/U DIN 41773-1

    Deep discharge protection and load rejection at

    19,8V DC ±0,4%

    Nominal output current

    40A DC

    Constant current limitation

    1,05...1,1xIANenn

    Battery type

    Pb-Akku, wartungsfrei
    Pb-Akku, wartungsarm

    efficiency

    (Ua=26,8V DC, Ia= Nom

    and Ue=400V AC)

    91,5% (typ.)

    max. power loss ‘worst-case’

    115W

    Earth leackage current

    <3,5mA

    Fusing primary

    3 x 4AT (external)

    fusing DC- output circuit

    40 A slow acting (external)

    Fusing battery load circuit

    40 A slow acting (external)

    Type of connection primary ‘mains’

    Combicon-screw type terminal 2,5mm2

    Fastening torque 0,5-0,6 Nm

    Type of connection secondary ‘Ua’, ‘UBatt’

    Screw type terminal 10mm2

    Fastening torque 1,2-1,5 Nm

    Type of connection interface
    ‘IO-1...IO-3’

    Combicon-screw type terminal 1,5mm2

    Fastening torque 0,22-0,25 Nm

    Type of connection Current-Share-Bus ‘CS’

    Combicon-screw type terminal 2,5mm2

    Fastening torque 0,5-0,6 Nm

    Display

    Netzbetrieb

    operation

    LED green illuminates:

    · Mains operation
    (UE>UEmin and TInt<TIntmax)

    LED green
    (battery voltage within the monitoring window 21,6< UBatt < 27,9V DC)

    LED green
    (battery voltage above the monitoring window UBatt =27V DC

    Fehler

    LED red
    LED illuminates at:

    * Battery operation (during mains operation LED is not illuminated)

    * Battery circuit interrupted respective high-ohmic (Testintervall 60s)

    * Battery low

    * Battery reverse poled

    * Battery-over-temperature (only in connection with temperature tracking

    Signal in- and outputs

    Mains operation 1)

    potentialfree relay-contact, closer, max. contact load 30 V DC/ 0,5A

    Fehler 1)

    potentialfree relay-contact, changer, max. contact load 30 V DC/ 0,5A

    1)

    potentialfree relay-contact, closer, max. contact load 30 V DC/ 0,5A

    1)

    potentialfree relay-contact, closer, max. contact load 30 V DC/ 0,5A

    Shut-Down

    Shut down of UPS mode

    Switch input, referring ot earth, switch level: 24V DC (16-80 V DC)

    Starkladung (Boost charging)

    Activation of boost charging (boost charging voltage 28.6 V DC)
    Switched input referenced to earth, switching level: 24V DC (16-80V DC)

    General

    weight

    appr. 3,3 kg

    storage

    recommended 0...30°C,
    permissible 0...50°C

    Operational temperature

    recommended 10...20°C (battery life duration!),

    permissible 0...40°C

    Protective system

    IP20

    dimensions

    290 x 180 x 147 mm (L x W x D)
    see section 10

    fixation

    Top hat rail according to DIN EN 50022-35
    Alternativ: assembly kit for direct screw fastening on the cabinet installation plate (option)

    UL approvals

    UL 508

    C22.2